ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Addressable Interface modules

Morley DRM-1 BS7273-4 Door Release Module

Current consumption without communication
310 μA @ 24 VDC (without communication)
Current consumption with communication
510 μA @ 24 VDC (communication every 5 sec with LED blink enabled)
Maximum alarm current
5 mA @ 24 VDC (per LED with LED enabled)
Operating voltage
15 to 30 VDC peak
Power supply
The module draws power from the door input supply
Auxiliary relay
Maximum rated continuous current 1 Amp; Maximum voltage 30V AC or DC
Operating temperature
-5°C to +45°C

You will also need

Needed to install, power or certify this product.

M200E-DIN

DIN rail mounting clip for M2xx series modules

Module must be mounted; DIN rail mounting option using the M200E-DIN clip.

£5.80
ex VAT
£6.96 inc VAT
Sold separately
SMB6-V0

Surface mount box for up to 6 M2xx modules

Modules must be enclosed; recommended custom enclosure holding up to 6 modules.

£40.07
ex VAT
£48.08 inc VAT
Sold separately

Overview

What it is and how it fits the system.

The Morley DRM-1 is a BS7273-4 door release module designed to work with the existing output module and wider fire system to meet section 5 requirements for Category A installations. It is also available as a standalone module for retrofit applications. Drawing power from the door input supply, it operates on 15 to 30VDC and includes an auxiliary relay rated 1A continuous at up to 30V AC or DC.

Technical overview

DRM-1 is a Morley Addressable Devices door release module in the Addressable Interface modules range and Door Module sub-range. It is designed to meet BS7273-4 section 5 requirements for Category A installations, working in conjunction with the existing output module and wider fire system, and can also serve as a standalone module for retrofit applications. The module operates on 15 to 30VDC peak, drawing power from the door input supply, and includes an auxiliary relay rated for 1 Amp continuous at up to 30V AC or DC.

A volt free contact switches mains through a third party relay, separating the fire system from direct mains connection, and the module is compatible with 12-24VDC door hold systems. It also provides dual time-delay settings compliant with BS7273-4 and an additional failsafe mechanism required by the section 5 code of practice. The required cable loom is supplied to integrate the device into the wider system.

The DRM-1 forms part of both the Morley-IAS Door Release System (MI-DRS-1) and the Notifier Door Release System (NFX-DRS-1). Modules must be housed in an enclosure: the unit can be mounted on a DIN rail using the M200E-DIN clip or installed in the SMB6-V0 surface mount box, which holds up to six modules.

Specifications

Full technical data for this part.

Current consumption without communication310 μA @ 24 VDC (without communication)
Current consumption with communication510 μA @ 24 VDC (communication every 5 sec with LED blink enabled)
Maximum alarm current5 mA @ 24 VDC (per LED with LED enabled)
Operating voltage15 to 30 VDC peak
Power supplyThe module draws power from the door input supply
Auxiliary relayMaximum rated continuous current 1 Amp; Maximum voltage 30V AC or DC
Loop input voltage rangeLoop input voltage range 15 to 30VDC
Maximum loop currentMaximum loop current 11μA @24V and 25°C
Max current draw from door supply35mA @12V (Auxiliary relay enabled); 25mA @12V (Auxiliary relay disabled); 25mA @24V (Auxiliary relay enabled); 20mA @24V (Auxiliary relay disabled)
Maximum door output continuous currentCurrent limited at 1Amp
Dimensions170mm(H) x 245mm(W) x 100mm(D)
Weight700g (Module only)
Maximum wire gauge2.5mm²
Operating temperature-5°C to +45°C

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Datasheets & documents

Reference downloads.