ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Morley ZXSe Panels

Morley 795-066 ZXe Loop driver card for Apollo Discovery or

connection_type
Plug-in connection
Dimensions
105 X 54 X 25 MM
Weight
44 GR.
Operating Temperature
0°C TO 49°C
loop_voltage
35V - signaling pulses
maximum_continuous_loop_drive_current
460mA (pulse signalling current)
Loop Capacity / Max per Loop
Up to 126 devices can be connected to a single loop driver card.

Specifications

Full technical data for this part.

connection_typePlug-in connection
Dimensions105 X 54 X 25 MM
Weight44 GR.
Operating Temperature0°C TO 49°C
Relative Humidity85% non- condensing
loop_voltage35V - signaling pulses
Power Consumption12mA (excluding loop devices)
maximum_continuous_loop_drive_current460mA (pulse signalling current)
maximum_circuit_rating_resistance100 Ohm max.
double_address_detection_noteDouble address detection cannot be guarantee with a loop resistance > 40 Ohms
maximum_circuit_rating_capacitance0.5μF max.
diagnosticsTwo diagnostic LEDs to indicate which end of the loop is being driven
loop_terminationsScrew terminals on the motherboard for a maximum cable cross sectional area of 2.5mm2 (13AWG) removable block.
wiringClass A or class B with shielded, twisted wire
loop_providedProvides one class-A or class-B loop
Loop Capacity / Max per LoopUp to 126 devices can be connected to a single loop driver card.
device_addressingAllows a unique address, in the range 001 to 126, to be selected
short_circuit_isolationShort-circuit isolation and double address detection are built into the plug in card.
analogue_monitoringThe loop driver continuously monitors the analogue values of all sensors and displays this value on the panel as a percentage of the alarm threshold value.

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know