Morley-IAS ZXe Loop driver card for Apollo Discovery or XP95 protocol
| Part no. | 795-066 |
|---|---|
| Brand | Morley-IAS |
| Range | Morley ZXSe Panels |
| Sub-range | Loop Card |
Image for illustration; item supplied may differ
At a glance
- Apollo Discovery And XP95795-066 is an Apollo XP95 and Discovery series loop driver card.
- Plug-In Loop Driver CardIt is a plug-in loop driver card that drives loop devices working to Apollo Discovery or XP95 Protocols.
- Loop Drive CurrentMaximum continuous loop drive current is 250mA (continuous) per driver.
- Card Power ConsumptionPower consumption is 40mA (excluding loop devices).
- Loop VoltageLoop voltage at the card is >25 V + signaling pulses.
- Maximum Circuit RatingsThe loop circuit is rated at 36 Ohm max. resistance and 0.6 µ F max. capacitance.
- Communication LEDOne LED indicates communication with a device.
- Size Weight And EnvironmentThe card is 90 x 54 x 25 mm, weighs 32 gr. (1 oz), and runs from 0°C to 49°C at 10% to 93% non-condensing humidity.
Description
Two Apollo protocols are open to this card, Discovery and XP95, and loop devices built for either can be driven from it.
Consumption at the card itself is 40mA (excluding loop devices), while drive reaches 250mA (continuous) per driver and the loop runs at >25 V + signaling pulses. Ceilings on the circuit are 36 Ohm max. resistance and 0.6 µ F max. capacitance, and a single LED signals communication with a device.
795-066 is an Apollo XP95 and Discovery series loop driver card. It plugs in as a loop driver card and works to Apollo Discovery or XP95 Protocols, driving loop devices built for either protocol. The card measures 90 x 54 x 25 mm and weighs 32 gr. (1 oz).
On the electrical side the card drives its loop at >25 V + signaling pulses while drawing 40mA (excluding loop devices) itself. Maximum continuous loop drive current is 250mA (continuous) per driver. The loop circuit it will work into is rated at 36 Ohm max. resistance and 0.6 µ F max. capacitance.
Read the full technical description
Physically it measures 90 x 54 x 25 mm and weighs 32 gr. (1 oz), specified from 0°C to 49°C at 10% to 93% non-condensing humidity.
795-066 is an Apollo XP95 and Discovery series loop driver card. It plugs in as a loop driver card and works to Apollo Discovery or XP95 Protocols, driving loop devices built for either protocol. The card measures 90 x 54 x 25 mm and weighs 32 gr. (1 oz).
On the electrical side the card drives its loop at >25 V + signaling pulses while drawing 40mA (excluding loop devices) itself. Maximum continuous loop drive current is 250mA (continuous) per driver. The loop circuit it will work into is rated at 36 Ohm max. resistance and 0.6 µ F max. capacitance.
One LED on the card indicates communication with a device. Operating conditions run from 0°C to 49°C at 10% to 93% non-condensing humidity.
Specifications
| Connection type | Plug-in connection |
|---|---|
| Dimensions | 105 X 54 X 25 MM |
| Weight | 44 GR. |
| Operating temperature | 0°C TO 49°C |
| Relative humidity | 85% non- condensing |
| Loop voltage | 35V - signaling pulses |
| Power Consumption | 12mA (excluding loop devices) |
| Maximum continuous loop drive current | 460mA (pulse signalling current) |
| Maximum circuit rating resistance | 100 Ohm max. |
| Double address detection note | Double address detection cannot be guarantee with a loop resistance > 40 Ohms |
| Maximum circuit rating capacitance | 0.5μF max. |
|---|---|
| Diagnostics | Two diagnostic LEDs to indicate which end of the loop is being driven |
| Loop terminations | Screw terminals on the motherboard for a maximum cable cross sectional area of 2.5mm2 (13AWG) removable block. |
| Wiring | Class A or class B with shielded, twisted wire |
| Loop provided | Provides one class-A or class-B loop |
| Loop Capacity / Max per Loop | Up to 126 devices can be connected to a single loop driver card. |
| Device addressing | Allows a unique address, in the range 001 to 126, to be selected |
| Short circuit isolation | Short-circuit isolation and double address detection are built into the plug in card. |
| Analogue monitoring | The loop driver continuously monitors the analogue values of all sensors and displays this value on the panel as a percentage of the alarm threshold value. |
Specifications per manufacturer documentation, subject to change. E&OE.