ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Gas Detection XCL

VESDA Sensepoint XCL XCL-VEA-H2-RA-5 Hydrogen 5-Pack

Ordering code description
5 x VESDA Sensepoint XCL H 1000ppm 4-20mA Relay for VEA
Gas detected
Hydrogen (H₂): 1000ppm
Supply voltage
24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum power consumption 24v dc
1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO₂); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO₂); Relay Version: additional 0.6W total
Maximum inrush current 24v dc
850 mA
Ingress protection
IP65, Type 4 (NEMA 250)
Operating temperature
−20 to +50 °C (−4 to +122 °F)

Overview

What it is and how it fits the system.

The XCL-VEA-H2-RA-5 is a pack of five VESDA Sensepoint XCL aspirated hydrogen (H2) gas detectors for the VESDA-E VEA micro bore network, each with a 1000ppm range and 4-20mA plus relay output. The charcoal polycarbonate units are rated IP65 (Type 4 / NEMA 250) and measure 113 x 113 x 59 mm at 500 g each.

Technical overview

XCL-VEA-H2-RA-5 is the five-detector ordering code for the Xtralis VESDA Sensepoint XCL aspirated hydrogen gas detector in 4-20 mA relay form, each unit covering hydrogen at 1000 ppm on a VESDA-E VEA micro bore tube network. Every detector in the pack inserts in-line, connecting to micro bore tube of 6 mm (1/4 in) OD through flexible tubes.

Interfaces are common across the five: integration with fire alarm control panels, PLCs, HVAC and building management systems, configurable relays, VSC and VSM4 remote detector access, and Bluetooth 4.0 (Bluetooth Low Energy) configuration from a compatible smart device running iOS 10 or Android 4.3 or above. Approvals span electrical safety (Conforms to EN/UL/IEC61010-1; Certified to CSA-C22.2 No. 61010-1-12), EMC (CE - EMC; EN 50270) and radio (RED, FCC, BT SIG).

Sensor exchange on any of the detectors uses the XCL-XRL-SC-H2 replacement hydrogen sensor, and the accessory range spans the XCL-FILTER replacement filter, XCL-VEA-CAL calibration/flow cap, XCL-M20-CG cable glands, XCL-VEA-TUB tubing interface and XCL-COVER sensor cover with gasket. Each unit terminates its field cabling in pluggable rising clamp connections.

Specifications

Full technical data for this part.

Ordering code description5 x VESDA Sensepoint XCL H 1000ppm 4-20mA Relay for VEA
Gas detectedHydrogen (H₂): 1000ppm
Supply voltage24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum power consumption 24v dc1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO₂); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO₂); Relay Version: additional 0.6W total
Maximum inrush current 24v dc850 mA
OutputAnalog Output: 0 to 22 mA; Digital Output: Modbus RTU; Relay Output: 2 relays (24 V DC / 250 V AC, 5 A)
Dimensions wxhxd113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
Weight500 g (1.1 lb)
Ingress protectionIP65, Type 4 (NEMA 250)
Casing materialPolycarbonate (charcoal colour)
Operating temperature−20 to +50 °C (−4 to +122 °F)
Storage temperature0 to +30 °C (+32 to +86 °F)
Humidity0 to 99% (non-condensing)
Atmospheric pressure95 to 110 kPa

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Spares & replacement parts

Replacement parts for units already in service.

XCL-XRL-SC-H2

XCL/XRL Replacement Sensor Hydrogen (H2)

Replacement H2 sensor cartridge for the XCL H2 detector.

£346.15
ex VAT
£415.38 inc VAT
Sold separately