ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Gas Detection XCL

VESDA Sensepoint XCL XCL-VEA-CO-RA-5 CO Detector 5-Pack

Ordering code description
5 x VESDA Sensepoint XCL CO 300ppm 4-20mA Relay for VEA
Gas detected
Carbon Monoxide (CO): 300ppm (adjustable 50 – 1000ppm)
Supply voltage
24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum power consumption 24v dc
1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO2); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO2); Relay Version: additional 0.6W total
Maximum inrush current 24v dc
850 mA
Ingress protection
IP65, Type 4 (NEMA 250)
Operating temperature
−20 to +50 °C (−4 to +122 °F)

Overview

What it is and how it fits the system.

The XCL-VEA-CO-RA-5 is a pack of five VESDA Sensepoint XCL aspirated carbon monoxide (CO) gas detectors for the VESDA-E VEA micro bore network, each set to 300ppm and adjustable from 50 to 1000ppm with 4-20mA and relay output. The charcoal polycarbonate units are rated IP65 (Type 4 / NEMA 250) and measure 113 x 113 x 59 mm at 500 g each.

Technical overview

XCL-VEA-CO-RA-5 equips five sampling positions from a single ordering code, covering five Xtralis VESDA Sensepoint XCL carbon monoxide detectors in 4-20 mA relay form for VESDA-E VEA Addressable Aspirating Smoke Detection installations on both new and existing systems.

Each detector splices into the VEA micro bore tube network with flexible tubing, drawing its sample from the 6 mm outside-diameter line, and monitors carbon monoxide against an adjustable measuring point. Alarm status reads on integral LEDs, and each unit connects over Bluetooth 4.0 (Bluetooth Low Energy) to a compatible smart device on iOS 10 or Android 4.3 and above, at up to 10 m depending on the mobile device.

Configurable relays and the analogue output feed fire alarm control panels, PLCs, HVAC and building management systems, and VSC and VSM4 handle remote detector access. Sensor renewal per unit uses the XCL-XRL-SC-CO replacement CO cartridge; approvals list UL2075 (CO and CH4), AS 1668.2 and EN 50270, and the installation manual carries the terminal-by-terminal wiring.

Specifications

Full technical data for this part.

Ordering code description5 x VESDA Sensepoint XCL CO 300ppm 4-20mA Relay for VEA
Gas detectedCarbon Monoxide (CO): 300ppm (adjustable 50 – 1000ppm)
Supply voltage24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum power consumption 24v dc1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO2); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO2); Relay Version: additional 0.6W total
Maximum inrush current 24v dc850 mA
OutputAnalog Output: 0 to 22 mA; Digital Output: Modbus RTU; Relay Output: 2 relays (24 V DC / 250 V AC, 5 A)
Dimensions wxhxd113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
Weight500 g (1.1 lb)
Ingress protectionIP65, Type 4 (NEMA 250)
Casing materialPolycarbonate (charcoal colour)
Operating temperature−20 to +50 °C (−4 to +122 °F)
Storage temperature0 to +30 °C (+32 to +86 °F)
Humidity0 to 99% (non-condensing)
Atmospheric pressure95 to 110 kPa

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Spares & replacement parts

Replacement parts for units already in service.

XCL-XRL-SC-CO

XCL/XRL Replacement Sensor - Oxygen (O2)

Replacement CO sensor cartridge for the XCL CO detector.

£248.98
ex VAT
£298.78 inc VAT