ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Gas Detection XCL

Xtralis XCL-VEA-CO-RA VESDA XCL CO for VEA

Ordering code description
VESDA Sensepoint XCL CO 300ppm 4-20mA Relay for VEA
Gas type and range
Carbon Monoxide (CO): 300ppm (adjustable 50 – 1000ppm)
Supply voltage
24 VDC nominal
Supply voltage analog
11 to 32V DC (Analog 4-20 mA)
Supply voltage ac
24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum inrush current 24v dc
850 mA
Ingress protection
IP65, Type 4 (NEMA 250)

Overview

What it is and how it fits the system.

The XCL-VEA-CO-RA is a VESDA Sensepoint XCL aspirated carbon monoxide (CO) gas detector that inserts in-line into a VESDA-E VEA micro bore tube network, set to 300ppm and adjustable from 50 to 1000ppm. It delivers 0 to 22 mA analogue output plus two relays (24 V DC / 250 V AC, 5 A) and runs on 24V DC nominal.

Technical overview

XCL-VEA-CO-RA monitors carbon monoxide on VESDA-E VEA microbore tube networks as an Xtralis addressable aspirated gas detector from the VESDA Sensepoint XCL range, signalling over a 4-20 mA loop with relay outputs. The measuring point is set to 300 ppm as standard and can be adjusted between 50 ppm and 1000 ppm.

The CO sensing cartridge is a cross-platform part: XCL-XRL-SC-CO serves both the XCL and XRL detector lines at the 300 ppm rating. Configuration happens over Bluetooth Low Energy from a compatible smart device up to 10 m away, alarm status shows on integral LEDs, and the relay pair alongside the analogue signal connects fire alarm control panels, PLCs, HVAC and building management systems, with VSC and VSM4 integration for remote access over Modbus.

Where a project calls for several detectors, XCL-VEA-CO-RA-5 covers the same unit as a five-piece multipack. Accessory support spans the XCL-VEA-CAL calibration and flow cap, XCL-VEA-TUB tubing interface, XCL-FILTER filters, XCL-M20-CG cable glands and XCL-COVER sensor cover with gasket. UL2075 (CO and CH4) and AS 1668.2 appear among the approvals with EN 50270 for EMC, and physical wiring is handled terminal by terminal in the installation manual.

Specifications

Full technical data for this part.

Ordering code descriptionVESDA Sensepoint XCL CO 300ppm 4-20mA Relay for VEA
Gas type and rangeCarbon Monoxide (CO): 300ppm (adjustable 50 – 1000ppm)
Supply voltage24 VDC nominal
Supply voltage analog11 to 32V DC (Analog 4-20 mA)
Supply voltage ac24V AC 50/60Hz Nominal (20 to 27 VAC)
Max power consumption 24v dc1.2 W (Analog 4-20mA) (toxic)
Relay version additional powerRelay Version: additional 0.6W total
Maximum inrush current 24v dc850 mA
Analog outputAnalog Output: 0 to 22 mA
Relay outputRelay Output: 2 relays (24 V DC / 250 V AC, 5 A)
Dimensions wxhxd113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
Weight500 g (1.1 lb)
Ingress protectionIP65, Type 4 (NEMA 250)
Casing materialPolycarbonate (charcoal colour)

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Spares & replacement parts

Replacement parts for units already in service.

XCL-XRL-SC-CO

XCL/XRL Replacement Sensor - Oxygen (O2)

Replacement CO sensor cartridge for the XCL CO detector.

£248.98
ex VAT
£298.78 inc VAT
Sold separately