Gas Detection XCL

VESDA Sensepoint XCL XCL-LB-H2-RM Hydrogen Modbus Detector

Product family
VESDA Sensepoint XCL – Large Bore
Nominal DC input voltage
24 V DC
Inrush current
Less than 850 mA
Sensor type
Electrochemical-cell-type
Operating temperature
−20 to 50 °C (−4 to 122 °F) °C
IP rating
IP65
EMC standard
EN 50270:2015

Overview

What it is and how it fits the system.

The XCL-LB-H2-RM is a VESDA Sensepoint XCL Large Bore hydrogen (H2) gas detector covering a 1000PPM range. Modbus digital output and an onboard relay enable networked hydrogen reporting together with local alarm switching from a single Large Bore unit.

Technical overview

XCL-LB-H2-RM is the Xtralis hydrogen detector in the VESDA Sensepoint XCL Large Bore range built for Modbus networks, sensing H2 to 1000PPM through an electrochemical cell. Concentration data passes upstream as Modbus RTU traffic while the relay contacts take care of local switching, combining networked H2 reporting with alarm response at the point of detection.

Compliance references on this Large Bore unit span EN 50270:2015 for EMC and safety conformity to UL 61010-1, CSA C22.2 No. 61010-1, IEC/EN 61010-1. Xtralis stands behind the detector with a parts-and-workmanship warranty.

Configuration is handled by the Sensepoint App, and the XCL-XRL-SC-H2 replacement cartridge restores hydrogen sensing when the cell is due for change; the same spare is referenced for XCL and XRL detectors alike. For physical wiring and terminal connections, the VESDA Sensepoint XCL Large Bore Installation Manual is the working reference.

Specifications

Full technical data for this part.

DescriptionVESDA XCL LB H 2 1000PPM MODBUS REL
Product familyVESDA Sensepoint XCL – Large Bore
WarrantyXtralis warrants the VESDA Sensepoint XCL gas detector against defective parts and workmanship.
Length113 mm (4.4 in) mm
Width113 mm (4.4 in) mm
Height59 mm (2.3 in) mm
Weight500 g (1.1 lb) g
Nominal DC input voltage24 V DC
Nominal AC input voltage24 V AC, 50/60 Hz V AC
DC operating voltage range (Modbus version)9 to 32 V DC
Inrush currentLess than 850 mA
Digital outputModbus RTU
Modbus baud rate (default)9600 bps
Relay output rating5 A, 250 V AC, 24 V DC
Sensor typeElectrochemical-cell-type
Power consumption (digital output version)0.3 W normal state, 0.7 W during alarm W
Additional power consumption (relay output version)0.6 W
Operating temperature−20 to 50 °C (−4 to 122 °F) °C
Storage temperature0 to 30 °C (32 to 86 °F) °C
Humidity0 to 99% (non-condensing) %
Atmospheric pressure90 to 110 kPa
IP ratingIP65
EMC standardEN 50270:2015
Electrical safetyUL 61010-1, CSA C22.2 No. 61010-1, IEC/EN 61010-1

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Spares & replacement parts

Replacement parts for units already in service.

XCL-XRL-SC-H2

XCL/XRL Replacement Sensor Hydrogen (H2)

Replacement H2 sensor cartridge XCL-XRL-SC-H2 (VESDA XCL XRL RPL SENS H 2 1000PPM)

£346.15
ex VAT
£415.38 inc VAT
Sold separately