Gas Detection XCL
VESDA Sensepoint XCL XCL-LB-H2-RM Hydrogen Modbus Detector
- Product family
- VESDA Sensepoint XCL – Large Bore
- Nominal DC input voltage
- 24 V DC
- Inrush current
- Less than 850 mA
- Sensor type
- Electrochemical-cell-type
- Operating temperature
- −20 to 50 °C (−4 to 122 °F) °C
- IP rating
- IP65
- EMC standard
- EN 50270:2015
Overview
What it is and how it fits the system.
The XCL-LB-H2-RM is a VESDA Sensepoint XCL Large Bore hydrogen (H2) gas detector covering a 1000PPM range. Modbus digital output and an onboard relay enable networked hydrogen reporting together with local alarm switching from a single Large Bore unit.
Technical overview
XCL-LB-H2-RM is the Xtralis hydrogen detector in the VESDA Sensepoint XCL Large Bore range built for Modbus networks, sensing H2 to 1000PPM through an electrochemical cell. Concentration data passes upstream as Modbus RTU traffic while the relay contacts take care of local switching, combining networked H2 reporting with alarm response at the point of detection.
Compliance references on this Large Bore unit span EN 50270:2015 for EMC and safety conformity to UL 61010-1, CSA C22.2 No. 61010-1, IEC/EN 61010-1. Xtralis stands behind the detector with a parts-and-workmanship warranty.
Configuration is handled by the Sensepoint App, and the XCL-XRL-SC-H2 replacement cartridge restores hydrogen sensing when the cell is due for change; the same spare is referenced for XCL and XRL detectors alike. For physical wiring and terminal connections, the VESDA Sensepoint XCL Large Bore Installation Manual is the working reference.
Specifications
Full technical data for this part.
| Description | VESDA XCL LB H 2 1000PPM MODBUS REL |
|---|---|
| Product family | VESDA Sensepoint XCL – Large Bore |
| Warranty | Xtralis warrants the VESDA Sensepoint XCL gas detector against defective parts and workmanship. |
| Length | 113 mm (4.4 in) mm |
| Width | 113 mm (4.4 in) mm |
| Height | 59 mm (2.3 in) mm |
| Weight | 500 g (1.1 lb) g |
| Nominal DC input voltage | 24 V DC |
| Nominal AC input voltage | 24 V AC, 50/60 Hz V AC |
| DC operating voltage range (Modbus version) | 9 to 32 V DC |
| Inrush current | Less than 850 mA |
| Digital output | Modbus RTU |
| Modbus baud rate (default) | 9600 bps |
| Relay output rating | 5 A, 250 V AC, 24 V DC |
| Sensor type | Electrochemical-cell-type |
| Power consumption (digital output version) | 0.3 W normal state, 0.7 W during alarm W |
| Additional power consumption (relay output version) | 0.6 W |
| Operating temperature | −20 to 50 °C (−4 to 122 °F) °C |
| Storage temperature | 0 to 30 °C (32 to 86 °F) °C |
| Humidity | 0 to 99% (non-condensing) % |
| Atmospheric pressure | 90 to 110 kPa |
| IP rating | IP65 |
| EMC standard | EN 50270:2015 |
| Electrical safety | UL 61010-1, CSA C22.2 No. 61010-1, IEC/EN 61010-1 |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Spares & replacement parts
Replacement parts for units already in service.
XCL/XRL Replacement Sensor Hydrogen (H2)
Replacement H2 sensor cartridge XCL-XRL-SC-H2 (VESDA XCL XRL RPL SENS H 2 1000PPM)