ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

VTT-10000 · Aspirating Smoke Detection

Xtralis VTT-10000-UK VESDA ASD Test Transformer, IP30

Type
VTT-10000
Ordering code
VTT-10000-UK United Kingdom
Voltage input
220-240 VAC, 50 Hz or 110-120 VAC, 60 Hz
Input rating
800 mA @ 240 VAC, 50 Hz, 1.6 A @ 120 VAC, 60 Hz
Output
6 VAC nominal, 20 A (7.3V nominal with no load)
Fuse
220-240 VAC, use: T 800 mA H 250V 20x5mm; 110-120 VAC, use: T 1.6 A H 125V 20x5mm (Where T indicates anti-surge & H high rupture capability)
Ingress protection
IP30 Indoor use only (this product is not to be used in the presence of moisture)

You will also need

Needed to install, power or certify this product.

251-001

Test Wire 100m

uses 251-001 Test Wire (100m) to perform wire-burn test

£31.45
ex VAT
£37.74 inc VAT
Sold separately

Overview

What it is and how it fits the system.

The Xtralis VTT-10000-UK is the United Kingdom ordering variant of the VTT-10000 Test Transformer (formerly the Hot Wire Test PSU), used to test very early warning aspirating smoke detection equipment by passing a high current through a test cable to heat it. Accepting 220-240 VAC at 50 Hz or 110-120 VAC at 60 Hz, it delivers a 6 VAC nominal, 20 A output with a selectable burn period of up to 3 minutes, a maximum on-time of 180 seconds and a minimum 7-minute off-time between tests.

Technical overview

VTT-10000-UK is the United Kingdom ordering variant of the Xtralis VTT-10000 test transformer, formerly known as the Hot Wire Test power supply unit and used to test very early warning aspirating smoke detection equipment. The transformer passes a high current through a test cable so that the wire heats, with a burn period selectable to a maximum of 3 minutes.

Protection and timing discipline are built in. An embedded thermal switch guards against over-temperature and blocks extended running whether or not power remains present, while turning the switch off resets the timer, ready to run the set period at the next switch-on. Green and red indicators show at a glance whether the output and its timer are active.

Wire-burn testing uses the 251-001 test wire, a 100 m length of PVC-insulated 10/0.1 mm strand wire matched to the transformer.

Safety approvals cover EN 61558-1:1997 and EN 61558-2-6:1997, with electromagnetic compatibility to EN 50081-1, EN 50082-1 and FCC Part 15 Class A Emissions. As a class A product for emissions, use in domestic surroundings may call for measures against radio interference, and compliant design, installation and commissioning follow the product guide.

Specifications

Full technical data for this part.

TypeVTT-10000
Ordering codeVTT-10000-UK United Kingdom
Voltage input220-240 VAC, 50 Hz or 110-120 VAC, 60 Hz
Input rating800 mA @ 240 VAC, 50 Hz, 1.6 A @ 120 VAC, 60 Hz
Output6 VAC nominal, 20 A (7.3V nominal with no load)
Fuse220-240 VAC, use: T 800 mA H 250V 20x5mm; 110-120 VAC, use: T 1.6 A H 125V 20x5mm (Where T indicates anti-surge & H high rupture capability)
Operating timeMaximum on time: 3 minutes (180 seconds)
Minimum off time between tests7 minutes (420 seconds)
Burn periodselectable burn period of up to 3 minutes
Ingress protectionIP30 Indoor use only (this product is not to be used in the presence of moisture)
Dimensions lxwxh7.2 cm x 12.1 cm x 13.3 cm
Weight2.7 kg
Thermal switchEmbedded thermal switch to protect against over-temperatures; regardless of the power presence, this switch will not allow operation for an extended period

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know