VESDA Remote Modules
VESDA VRT-W00 VLF Remote Display, No Relays
- Ordering code
- VRT-W00 — VESDA VLF No Relays
- Supply voltage
- 18-30 VDC
- Operating temperature
- 0° to 39°C (32° to 103°F)
- Humidity
- 10-99% RH non-condensing
- Alarm indicators
- High Intensity LEDs with 70 degree viewing angle
- Display
- 20-Segment Vertical Bar Graph Display with 2 digit numeric display, clear alarm and fault indicators, and built-in sounder
- Push button keys
- 4 push button keys (Mode/Test, Silence/Scan, Reset, Isolate); can be disabled during commissioning (except Silence). A pressed key gives a short tone when enabled and a long tone when disabled.
Overview
What it is and how it fits the system.
The Xtralis VRT-W00 is a VESDA display module for the VLF detector, supplied with no relays, providing real-time status indication of an assigned VESDA detector. It features a 20-segment vertical bar graph and 2-digit numeric display, a built-in audible sounder, high-intensity alarm LEDs with a 70-degree viewing angle, and 4 push-button keys (Mode/Test, Silence/Scan, Reset, Isolate). It runs on 18-30 VDC across 0-39 degC at 10-99% RH non-condensing, with a remote box measuring 140 x 150 x 85mm.
Technical overview
VRT-W00 is the no-relay version of the Xtralis VESDA remote display for the VLF detector, ordered in remote mounting box format and assigned to a single VESDA detector zone for immediate status reporting and zone control.
Connection runs over VESDAnet, and fault indication distinguishes three levels: system-wide faults reaching any device on VESDAnet, zone-level faults local to the assigned detector and its displays, and urgent faults calling for an immediate response.
Status presents on a 20-segment vertical bar graph paired with a two-digit numeric readout, supported by a built-in sounder and high-intensity alarm LEDs giving a 70-degree viewing angle.
The VSP-012 recessed mounting kit is an optional accessory for the remote box, while VRT-V00 offers the same VLF display with 7 relays where relay outputs are required.
Specifications
Full technical data for this part.
| Ordering code | VRT-W00 — VESDA VLF No Relays |
|---|---|
| Supply voltage | 18-30 VDC |
| Operating temperature | 0° to 39°C (32° to 103°F) |
| Humidity | 10-99% RH non-condensing |
| Alarm indicators | High Intensity LEDs with 70 degree viewing angle |
| Display | 20-Segment Vertical Bar Graph Display with 2 digit numeric display, clear alarm and fault indicators, and built-in sounder |
| Push button keys | 4 push button keys (Mode/Test, Silence/Scan, Reset, Isolate); can be disabled during commissioning (except Silence). A pressed key gives a short tone when enabled and a long tone when disabled. |
| Fault indicators | System (a fault that affects the whole VESDA system, any devices connected on VESDAnet); Zone (a fault that affects only the assigned VESDA detector and its associated displays); Urgent (a serious fault requiring immediate attention) |
| Dimensions whd remote box | 140 mm x 150 mm x 85 mm (5.5 in x 5.9 in x 3.4 in) |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
VLF Remote Display with Relays
Alternative — same VESDA VLF display module in remote mounting box, with 7 relays instead of no relays.