VESDA Remote Display for Marine Approved Applications · VESDA Remote Modules

VESDA VRT-J00 Marine Compact Remote Display

Product type
VESDA Remote Display for Marine Approved Applications
Full part code
VRT-J0000-MRN
Document number
Doc. no. 11687_04 Part: 20524
Indicators
alarm, fault and smoke bargraph indicators
Integral sounder
the unit supports an integral sounder
Status reflection
reflects the status of the VESDA detector VLC-50500-MRN when connected
Marine approval caution
Failure to comply with these Installation Instructions invalidates the marine approval for these products

Overview

What it is and how it fits the system.

The Xtralis VRT-J0000-MRN is the marine version of the Compact Remote Display, providing real-time indication of smoke level, alarm and fault status for a VESDA VLC detector and reflecting the status of the connected VLC-50500-MRN. It carries alarm, fault and smoke bargraph indicators plus an integral sounder. For marine environments, additional EMC protection is required and two ferrites (P/N 0443167251) come pre-installed on the grey cable loop; failure to follow the installation instructions invalidates the marine approval.

Specifications

Full technical data for this part.

Product typeVESDA Remote Display for Marine Approved Applications
Full part codeVRT-J0000-MRN
Document numberDoc. no. 11687_04 Part: 20524
Indicatorsalarm, fault and smoke bargraph indicators
Integral sounderthe unit supports an integral sounder
Status reflectionreflects the status of the VESDA detector VLC-50500-MRN when connected
Marine emc protectionWhen installed in a Marine environment additional EMC protection is required to ensure a safe margin of emissions in the frequency range 156 - 165 MHz, provided by the incorporation of 3 ferrite bead components
Ferrite componentsTwo small ferrites (P/N 0443167251) pre-installed on the grey cable looms, plus an additional larger ferrite (P/N 0431173551) installed around all cables just before they exit the unit
Marine approval cautionFailure to comply with these Installation Instructions invalidates the marine approval for these products