VESDA Metal Box HLI - Modbus Type 2

Part no.VHX-1410
BrandVESDA
RangeVESDA Programming and Connectivity
VESDA VHX-1410 Wall-Mounted ModBus HLI Type 2 — grey top with VESDA High Level Interface text, black base, front CE label.

Image for illustration; item supplied may differ

At a glance

  • Wall-Mounted ModBus Type 2This is the Type 2 ModBus HLI, wall-mounted, in the VESDA MODBUS HLI range.
  • Echoing Function DisabledThis variant has the echoing function disabled.
  • Address Range In NetworksThe range is carved into 7 logical networks, network 1 taking the first 30 addresses and network 2 the addresses between 31 to 60.
  • VESDAnet Fault MappingEvery VESDAnet fault lands on one or more Modbus HLI faults: Head Fault on its own, Head Fault qualified as Battery and Mains or as Scanner, and Flow Fault.
  • Zone And Network FaultsA fault treated as a network fault reaches all zones, while a zone fault stays on the zone it belongs to.
  • Host Information AvailableThe host can read Detector Alarm State - Alert, Action, Fire - along with Smoke Level, Smoke Bargraph Level and the detector alarm thresholds.
  • Detector Type And Mimic ModeThe Detector Type reported covers VLP, VLS, VLC and VLF, with Support Mimic Mode for VLP/VLC/VLS.

Description

The Type 2 build of the wall-mounted ModBus HLI is the one whose echoing function is disabled.

The Detector Type reported covers VLP, VLS, VLC and VLF, with Support Mimic Mode for VLP/VLC/VLS. Fault Status sent back separates Head, Battery and Mains, Flow and Scanner conditions.

Wall-mounted and with its echoing function disabled, VHX-1410 is the Type 2 build of the VESDA Wall-mounted ModBus High Level Interface. Any host that speaks the ModBus protocol reaches a VESDAnet through it.

Addressing carves the range into 7 logical networks, network 1 taking the first 30 addresses, network 2 the addresses between 31 to 60, and so on.

Read the full technical description

The role recommended for a VESDA HLI is secondary monitoring, and primary reporting to a fire panel, or to a different primary reporting system, is also suitable; taken on for primary reporting, the interface must be integrated with, and approved or listed with, the panel or system it serves, to whatever fire standards and codes are in force.

Wall-mounted and with its echoing function disabled, VHX-1410 is the Type 2 build of the VESDA Wall-mounted ModBus High Level Interface. Any host that speaks the ModBus protocol reaches a VESDAnet through it.

Addressing carves the range into 7 logical networks, network 1 taking the first 30 addresses, network 2 the addresses between 31 to 60, and so on.

Every VESDAnet fault lands on one or more Modbus HLI faults: Head Fault on its own, Head Fault qualified as Battery and Mains or as Scanner, and Flow Fault. A fault treated as a network fault reaches all zones, while a zone fault stays on the zone it belongs to. The host can read Detector Alarm State - Alert, Action, Fire - along with Smoke Level, Smoke Bargraph Level and the detector alarm thresholds, and can issue the Reset Detector and Isolate Detector commands as well as Start Scan Test. A VESDA HLI is recommended to work in secondary monitoring; primary reporting is also suitable, but only where the interface has been integrated and approved or listed with the panel or reporting system that receives it, against the fire standards and codes that apply.

Specifications

Ordering codeVHX-1410
DescriptionModBus HLI - Type 2
TypeWall-mounted ModBus HLI Type 2 (VHX-1410) which has the echoing function disabled
MountingWall-mounted
Supply voltage24 VDC
Current consumption70 mA (Quiescent)
Power consumption1.68 W (Quiescent)
Dimensions280 mm x 185 mm x 55 mm (11.0 in. x 7.3 in. x 2.2 in. approx.)
Weight1.0 kg (2.2 lbs)
Supplied withVESDAlink RS-232 9-way serial cable (male-female)
Number of detectors supportedUp to 200 VESDA Devices (includes max 40 detectors and remaining VESDA ancillary devices)
Modem supportModem support is not available
Host interfaceRS-232
Mounting pointØ 6.5mm

Specifications per manufacturer documentation, subject to change. E&OE.