Part Number or the Week S3EP-V-VAD-HPR-R

VESDA Metal Box HLI - Modbus Type 1

Part no.VHX-1400
BrandVESDA
RangeVESDA Programming and Connectivity
VESDA VHX-1400 High Level Interface — grey-topped rectangular unit with black base, white label and CE mark on front.

Image for illustration; item supplied may differ

At a glance

  • Wall-Mounted Type 1 BuildVHX-1400 is the Wall-mounted ModBus HLI Type 1 High Level Interface.
  • Character Echo On RS232The Type 1 build sends each character it takes in on the RS232 link straight back to the host, with reply message.
  • Detector Count Per InterfaceA single VESDAnet served by one ModBus HLI carries as many as 40 VESDA detectors.
  • Zone NumberingAddressing uses detector zone numbers between 1 to 200 on the VESDAnet.
  • Address Range SplitThe address range is divided into 7 logical networks, the opening 30 addresses sitting in network 1 and the addresses between 31 to 60 in network 2.
  • Reported Threshold ValuesRelative to a sensitivity of 1 %obs/m, a Fire Alarm threshold of 2 %obs/m comes back as 50, 1 %obs/m as 100, 0.1 %obs/m as 1000 and 0.02 %obs/m as 5000.

Description

Wall mounting and the Type 1 echo behaviour are what define this unit.

Direct access to a VESDAnet, and monitoring of what sits on it, is what the interface delivers, and Xtralis configuring and monitoring software packages make it straightforward to set up. The host is told the Detector Type - VLP, VLS, VLC or VLF - and Mimic Mode is supported for VLP/VLC/VLS.

VHX-1400 is the Wall-mounted ModBus HLI Type 1, a VESDA Wall-mounted ModBus High Level Interface. A Fire Alarm Control Panel (FACP), a Building Management System (BMS) or PC software monitoring tools that support the ModBus protocol are joined to a VESDAnet through it, and as the Type 1 build it returns to the host every character arriving on its RS232 link, together with reply message.

A single VESDAnet, served by one ModBus HLI, holds as many as 40 VESDA detectors, addressed on detector zone numbers between 1 to 200 across that network. The address range is split into 7 logical networks: the opening 30 addresses sit in network 1, the addresses between 31 to 60 in network 2, and so on across the range.

Read the full technical description

The recommended duty for a VESDA HLI is secondary monitoring, covering fire alarms and the other notifications a VESDAnet delivers. Primary reporting is suitable as well, provided the interface has first been integrated into whichever panel or reporting system takes it on, and approved or listed with it, to the fire standards and codes applying at the site.

VHX-1400 is the Wall-mounted ModBus HLI Type 1, a VESDA Wall-mounted ModBus High Level Interface. A Fire Alarm Control Panel (FACP), a Building Management System (BMS) or PC software monitoring tools that support the ModBus protocol are joined to a VESDAnet through it, and as the Type 1 build it returns to the host every character arriving on its RS232 link, together with reply message.

A single VESDAnet, served by one ModBus HLI, holds as many as 40 VESDA detectors, addressed on detector zone numbers between 1 to 200 across that network. The address range is split into 7 logical networks: the opening 30 addresses sit in network 1, the addresses between 31 to 60 in network 2, and so on across the range.

Smoke Level comes back relative to the Fire Alarm threshold on a full scale of 20, so the reported smoke value multiplied by the Fire1 Threshold and divided by 20 gives the actual smoke level. Secondary monitoring is the role recommended for a VESDA HLI; primary reporting is also suitable, whether it goes to a fire panel or to some other primary reporting system, and calls for the unit to be integrated and approved or listed with whatever panel or system receives the report, to the relevant fire standards and codes.

Specifications

TypeModBus HLI - Type 1
Echo functionType 1 (VHX-1400) echoes each character received on the RS232 link back to the host together with reply message
Ordering codeVHX-1400
Supply voltage24 VDC
Current consumption70 mA (Quiescent)
Power consumption1.68 W (Quiescent)
Dimensions280 mm x 185 mm x 55 mm (11.0 in. x 7.3 in. x 2.2 in. approx.)
Weight1.0 kg (2.2 lbs)
Supplied withVESDAlink RS-232 9-way serial cable (male-female)
Number of detectors supportedUp to 200 VESDA Devices (includes max 40 detectors and remaining VESDA ancillary devices)
Modem supportModem support is not available
Host interfaceRS-232
MountingWall-mounted
Mounting pointMounting Point Ø 6.5mm