VESDA Metal Box HLI - Peer to Peer
| Part no. | VHX-1300 |
|---|---|
| Brand | VESDA |
| Range | VESDA Programming and Connectivity |

Image for illustration; item supplied may differ
At a glance
- Wall-Mounted Peer-To-Peer HLIVHX-1300 is the wall-mounted Open Protocol HLI (Peer-to-Peer).
- Built-In VESDAnet InterfaceA built-in VESDAnet interface means a remote VESDAnet socket module is not needed.
- Two-Way Link SupervisionBoth the HLI and host are responsible for supervising the communications link between them.
- Unsolicited Host MessagesThe HLI sends unsolicited messages to the host while the host polls it for information about devices on VESDAnet.
- Multiple Message RequestsIn the peer-to-peer model, the host can request and receive multiple messages from the HLI.
- Display Information ReportedDisplay info covers alarm thresholds and location name, and display update carries smoke level with alarm and fault status.
- Mimic Mode SupportMimic Mode is supported for VLP/VLC/VLS.
Description
Two-way supervision is the distinguishing feature here. Because the HLI raises messages of its own rather than waiting to be asked, the communications link is watched from both ends.
Detector Type (VLC, VLS, VLP, VLF) on VESDAnet is reported back to the host. The unit is wall-mounted and carries the VESDAnet interface on board.
VHX-1300 is the wall-mounted Open Protocol HLI (Peer-to-Peer) in the VESDA range, connecting a VESDAnet to the host - PC software monitoring tools, a Building Management System (BMS) or a Fire Alarm Control Panel (FACP). A built-in VESDAnet interface means a remote VESDAnet socket module is not needed.
In the peer-to-peer model, the host polls the HLI for information about devices on VESDAnet, while the HLI sends unsolicited messages to the host, so both the HLI and host are responsible for supervising the communications link between them. The host can also request and receive multiple messages from the HLI.
Read the full technical description
Secondary monitoring of fire alarms and other VESDAnet notifications is the recommended duty for VESDA HLIs, which are also suitable for primary reporting, whether to the fire panel or to another primary reporting system. Primary reporting requires the unit to be approved or listed with the receiving panel or system, and integrated into it, for the applicable fire standards and codes.
VHX-1300 is the wall-mounted Open Protocol HLI (Peer-to-Peer) in the VESDA range, connecting a VESDAnet to the host - PC software monitoring tools, a Building Management System (BMS) or a Fire Alarm Control Panel (FACP). A built-in VESDAnet interface means a remote VESDAnet socket module is not needed.
In the peer-to-peer model, the host polls the HLI for information about devices on VESDAnet, while the HLI sends unsolicited messages to the host, so both the HLI and host are responsible for supervising the communications link between them. The host can also request and receive multiple messages from the HLI.
Direct access and monitoring of your entire VESDAnet system is what the interface provides. Display info covers alarm thresholds and location name, display update carries smoke level with alarm and fault status, and Mimic Mode is supported for VLP/VLC/VLS. For a VESDA HLI the recommended application is secondary monitoring of fire alarms and other VESDAnet notifications; it is also suitable for primary reporting, whether that goes to a fire panel or to another primary reporting system, provided the unit has first been integrated with that panel or system and approved or listed with it, under the fire standards and codes that govern the installation.
Specifications
| Ordering code | VHX-1300 |
|---|---|
| Description | Open Protocol HLI (Peer-to-Peer) / Wall-mounted Open Protocol HLI (Peer-to-Peer) |
| Operating mode | Peer-to-Peer - the host polls the HLI for information about devices on VESDAnet, while the HLI sends unsolicited messages to the host; both the HLI and host are responsible for supervising the communications link |
| Power consumption | 1.68 W (Quiescent) |
| Supply voltage | 24 VDC |
| Current consumption | 70 mA (Quiescent) |
| Dimensions | 280 mm x 185 mm x 55 mm (11 in. x 7.3 in. x 2.2 in. approx.) |
| Weight | 2 kg (4.4 lbs) |
|---|---|
| Mounting point | Ø 6.5mm |
| Supplied with | VESDAlink RS-232 9-way serial cable (male-female) (identical to VSP-509) |
| Number of detectors supported | Up to 40 detectors* (If your network has more than 40 detectors, please contact your Xtralis representative) |
| Modem support | Modem support is not available |
| Interface | Built-in VESDAnet interface |
| Configuration software | Easily configured using Xtralis configuring and monitoring software packages |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- VHX-1310Metal Box HLI - Master-SlaveAlternative - the master-slave model of the same wall-mounted Open Protocol HLI.£2,489.18ex VAT£2,987.02 inc VATIn stock
Spares & replacement parts
- VSP-509LaserCOMPACT RO 9 Pin LeadVSP-509 VESDAlink RS-232 9-way serial cable (Spare part), identical to the cable supplied£77.63ex VAT£93.16 inc VATIn stock