Morley-IAS PLUS compact addressable fire panel
| Part no. | PL-1000 |
|---|---|
| Brand | Morley-IAS |
| Range | Morley Plus panel |
| Sub-range | Fire Panel |

Image for illustration; item supplied may differ
At a glance
- Single Loop Addressable PanelPL-1000 is a compact analogue-addressable fire alarm control panel with a single loop.
- Expandable To Two LoopsThe optional loop card PL-LIB01 expands the panel to a 2 loop system.
- 159 Devices Per LoopEach loop supports 159 detectors and 159 input / output modules.
- Advanced AP ProtocolThe panel works on Honeywell's Advanced (AP) protocol.
- Touch Screen Colour DisplayThe display is a 4.3“ touch-screen graphical colour display of 480 x 272 pixel with back illumination and back-lit membrane buttons.
- Mains Input And Battery CapacityMains input is 100-240 V AC +/- 15%, 50 / 60 Hz at a power consumption of max. 65W, and battery capacity is 7 Ah or 12 Ah (not included).
- Outputs And Sounder CircuitsThe panel carries 1 fault (NO/NC), 1 alarm (NO/NC), a 24 VDC output of max. 500 mA and sounder outputs of 2, max. 250 mA.
- EN54-2 And EN54-4 CertifiedThe panel is certified to EN54-2, EN54-4; LVD 62.368-1:2014+A11.
Description
PL-1000 occupies 356 x 379 x 120 mm (H X W X D), weighs 1.76 KG and is finished in RAL 9002 behind an IP30 enclosure. Its working envelope is 0°C to +40°C at 5% - 95% non-condensing humidity, and it is certified to EN54-2, EN54-4; LVD 62.368-1:2014+A11.
Where a second circuit is needed, the optional loop module PL-LIB01 turns the panel into a 2 loop system, with 159 detectors and 159 input / output modules carried on each loop. This is a compact panel that is easy to install and configure, its whole configuration being built from the screen itself.
Read the full technical description
PL-1000 is a compact analogue-addressable fire alarm control panel in the Morley-IAS Plus family, built around a single loop that can be taken to two loops with the optional PL-LIB01 loop card. Each loop supports 159 detectors and 159 input / output modules. Loop working is on Honeywell's Advanced (AP) protocol, which maximises the speed and efficiency of alarm detection.
The operator works at a 4.3“ touch-screen graphical colour display of 480 x 272 pixel, back illuminated, with back-lit membrane buttons. Full system configuration is done from that screen, helped by a simple DOT Matrix cause and effect rule builder and multiple language selections. Event handling is presented through a colour event indication tab system and an on-screen 16 Virtual Zonal LED indicator.
Mains input is 100-240 V AC +/- 15%, 50 / 60 Hz and power consumption is max. 65W, and battery capacity is 7 Ah or 12 Ah (not included). Field circuits comprise 1 fault (NO/NC) and 1 alarm (NO/NC), a 24 VDC output of max. 500 mA, and sounder outputs numbering 2, max. 250 mA.
Specifications
| Commercial part number | PL-1000 |
|---|---|
| Order part number | PL-1000 |
| Description | MORLEY PLUS 1 LOOP 159D+159I/O DEVICES |
| Loops | 1 LOOP |
| Device capacity | 159D+159I/O DEVICES |
| Product family | MORLEY PANEL PLUS |
| Unit of measure | ea |
| Lead time | 1W |
Specifications per manufacturer documentation, subject to change. E&OE.