Morley IM-10EA Ten-Input Monitor Module, Addressable

Dimensions
H147mm x W185mm x D25mm
voltage
15 to 32V
current_consumption
3.50mA (Blinking LED once every 5 seconds) 60mA at 32V assuming all ten LEDS solid on
current
92mA max at 32V
Addressing
The first address is set from 01 to 90; the other modules are automatically assigned the next nine addresses; up to four unused addresses can be disabled.
supervised_state
The supervised state: normal, open circuit fault or short circuit alarm is sent back to the control panel.

Overview

What it is and how it fits the system.

The Morley IM-10EA is a ten-input monitor module that provides an addressable interface to normally open contact devices. It is used to monitor signals such as plant outputs or flow switches across a fire detection system.

Technical overview

IM-10EA is a ten input monitor module in the Addressable Interface modules range, designed as an Input Module for normally open contact devices such as plant outputs or flow switches. It operates on a voltage range of 15 to 32V, with a current consumption of 3.50mA when the LED blinks once every five seconds and up to 60mA at 32V when all ten LEDs are solid on, reaching a maximum of 92mA at 32V.

The module measures H147mm x W185mm x D25mm and requires back box 797-065 for installation. Addressing is configured by setting the first address from 01 to 90, with subsequent modules automatically assigned the next nine addresses, allowing up to four unused addresses to be disabled. It communicates supervised state information—normal, open circuit fault, or short circuit alarm—back to the control panel.

Specifications

Full technical data for this part.

DimensionsH147mm x W185mm x D25mm
voltage15 to 32V
current_consumption3.50mA (Blinking LED once every 5 seconds) 60mA at 32V assuming all ten LEDS solid on
current92mA max at 32V
AddressingThe first address is set from 01 to 90; the other modules are automatically assigned the next nine addresses; up to four unused addresses can be disabled.
supervised_stateThe supervised state: normal, open circuit fault or short circuit alarm is sent back to the control panel.

Specifications sourced from manufacturer documentation.