Aspirating Smoke Detection

Xtralis F-PC-HE-6.5 ASD Sampling Clip 6.5mm Harsh Env

Order code description
ASD SPL PT CLIP HE 6.5mm (1/4)
Variant type
Harsh Environment
Length
55 mm
Weight
11 g
Width
30.5 mm
Tube outer diameter
25 mm - 27 mm
Colour body
RAL9005

Overview

What it is and how it fits the system.

The Xtralis F-PC-HE-6.5 is a Harsh Environment VESDA/FAAST sampling point hole clip from Honeywell's CLIP Hole Identification System, carrying a pre-engineered 6.5mm (1/4 inch) sampling hole. Constructed in PC/ABS with a RAL9005 body and a variable-material TPE seal, it fits tube of 25mm to 27mm outer diameter and supports a maximum pipe network pressure of 7 bar across -30C to +45C. Compact at 55mm by 30.5mm and 11g, it standardises sampling-point sizing in demanding environments.

Technical overview

F-PC-HE-6.5 marks a 6.5mm (1/4) sampling hole on VESDA aspirating smoke detection pipework, an Xtralis sampling point hole clip from a CLIP Hole Identification System range documented in both Standard and Harsh Environment formats. This part is the Harsh Environment version, carrying the flexi-lip design that sets those variants apart at the sampling hole.

Preparing the pipe run means creating every sampling hole with a 10mm (27/64") drill bit, after which the clip locates on ASD sampling pipe of 25 mm to 27 mm outer diameter. Every clip is a one-piece part.

Colour identification follows the IEC 60062 standard resistor code, separating the 6.5mm clip from other sizes across the same run. Connection and fitting detail is documented in the installation instructions, the reference for helping to ensure full functionality.

Specifications

Full technical data for this part.

Order code descriptionASD SPL PT CLIP HE 6.5mm (1/4)
Variant typeHarsh Environment
Length55 mm
Weight11 g
Width30.5 mm
Tube outer diameter25 mm - 27 mm
Colour bodyRAL9005
MaterialPC/ABS
Colour rubberVariable material TPE
Maximum pipe network pressure7 bar ( -30 °C +45 °C)
Application temperature range-30 °C +45 °C* (Application where ambient temperature will exceed 45°C may lead to clip sealing leakage up to 5%)
Application humidity range5% to 95% Relative Humidity
Sampling hole size6.5mm (1/4)
Supplied asAll parts are supplied as a single piece

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know