ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Aspirating Smoke Detection

Xtralis F-PC-HE-5 ASD Sampling Clip 5.0mm Harsh Env

Variant type
Harsh Environment
Sampling hole size
5.0mm (13/64)
Length
55 mm
Weight
11 g
Width
30.5 mm
Tube outer diameter
25 mm - 27 mm
Colour body
RAL9005

Overview

What it is and how it fits the system.

The Xtralis F-PC-HE-5 is a Harsh Environment sampling point hole clip from the VESDA/FAAST Sampling Hole Identification (CLIP) system, carrying a pre-engineered 5.0mm (13/64) sampling hole. Moulded in PC/ABS with a RAL9005 body, it fits tube of 25mm to 27mm outer diameter. At 55mm by 30.5mm and 11g, it provides a colour-coded, precisely sized sampling point for aspirating smoke detection.

Technical overview

F-PC-HE-5 provides the 5.0mm (13/64) Harsh Environment size in the VESDA Sampling Hole Clip range, an Xtralis sampling point hole clip within the Honeywell FAAST/VESDA Sampling Hole Identification (CLIP) System for aspirating smoke detection pipework.

Dusty conditions shape the design. A chamfered hole entry reduces dust loading effects, helping to increase uptime and potentially extending test intervals, and the moulding carries the flexi-lip design characteristic of the Harsh Environment clips.

Installers create 10mm (27/64") drill holes for all sampling points, then click each single-piece clip into position on tube of 25 mm to 27 mm outer diameter - an installation-ready design with no assembly and no tooling. Colour coding assigned accordingly to the IEC 60062 standard resistor code identifies the 5.0mm clip against other sizes, and the installation instructions carry the remaining fitting detail.

Specifications

Full technical data for this part.

Order codeF-PC-HE-5
DescriptionASD SPL PT CLIP HE 5.0mm (13/64)
Variant typeHarsh Environment
Sampling hole size5.0mm (13/64)
Length55 mm
Weight11 g
Width30.5 mm
Tube outer diameter25 mm - 27 mm
Colour bodyRAL9005
MaterialPC/ABS
Colour rubberVariable material TPE
Maximum pipe network pressure7 bar ( -30 °C +45 °C)
Application temperature range-30 °C +45 °C* (Application where ambient temperature will exceed 45°C may lead to clip sealing leakage up to 5%.)
Application humidity range5% to 95% Relative Humidity

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Datasheets & documents

Reference downloads.