ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Addressable Audio Visual Devices

Honeywell DSS-PC-I00 FS24X Plus Flame Detector

Operating voltage
24 VDC nominal (18-32 VDC) - Regulated.
Power consumption
1.8 watts (nominal); 2.4 watts (Alarm); 12 Watts (max) = 0.50A @ 24V with heater ON 100% duty cycle.
Inrush current
Inrush Current is 0.75A for a maximum duration of less than 5ms.
Outputs
Fault, Alarm and Auxiliary SPDT relays Max. 32 Vdc/ac, max. 2 A, min 10 mA at 12 V resistive load. 4-20 mA source, sink or isolated current output. Uncertainty is 1% of reading. FP2 over RS-485 and USB (USB is accessible through Detector Module electronic device only). Modbus over RS-485.
4-20 ma output
4-20 mA Source, sink or isolated current output.
Communications
FP2 over RS-485 and USB; Modbus over RS-485; HART® 7 communication registered with FieldComm Group, EDD/DTM files available.
Operating temperature north america
Operating Temperature (North America): -50°C to +75°C

Specifications

Full technical data for this part.

Operating voltage24 VDC nominal (18-32 VDC) - Regulated.
Power consumption1.8 watts (nominal); 2.4 watts (Alarm); 12 Watts (max) = 0.50A @ 24V with heater ON 100% duty cycle.
Inrush currentInrush Current is 0.75A for a maximum duration of less than 5ms.
OutputsFault, Alarm and Auxiliary SPDT relays Max. 32 Vdc/ac, max. 2 A, min 10 mA at 12 V resistive load. 4-20 mA source, sink or isolated current output. Uncertainty is 1% of reading. FP2 over RS-485 and USB (USB is accessible through Detector Module electronic device only). Modbus over RS-485.
4-20 ma output4-20 mA Source, sink or isolated current output.
CommunicationsFP2 over RS-485 and USB; Modbus over RS-485; HART® 7 communication registered with FieldComm Group, EDD/DTM files available.
WeightAluminum 3 lbs. 11 oz. (1.7 kg); Stainless Steel 7 lbs. 7 oz. (3.4 kg)
Housing materialLow Copper (less than 0.25%) marine grade Painted casted Aluminum of ASTM A356.0 grade. Polished cast Stainless Steel of ASTM CF8M grade.
EnclosureDiameter: 125 mm (4.92 in) x 115 mm (4.52 in) deep; Two M25 X 1.5P or two ¾'' NPT conduit entries.
Window sizeWindow size diameter: 79 mm (3.11 in)
Operating temperature north americaOperating Temperature (North America): -50°C to +75°C
Operating temperature atex iecexOperating Temperature (ATEX/IECEx): -55°C to +75°C
Storage temperature north americaStorage Temperature (North America): -50°C to +85°C
Storage temperature atex iecexStorage Temperature (ATEX/IECEx): -55°C to +85°C

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know