Addressable Interface modules

Morley CR-6EA 6-Way Changeover Relay Output Module

relay_type
The CR-6EA consists of six Form C relays
relay_contacts
A single isolated set of dry relay contacts, which can be wired as normally open or normally closed, is provided for each address
relay_contact_ratings
3A at 30VDC Resisitive Load
relay_current
30mA/relay pulse 15.6ms duration, pulse under panel control
maximum_current
1.49mA (Blinking LED once every 5 seconds) 36mA at 32V assuming all six relays have switched once and all six LEDs solid on
Addressing
The first address is set from 01 to 94; the other modules are automatically assigned the next five addresses; up to three unused addresses can be disabled
supervision
The controlled circuit is not supervised

Overview

What it is and how it fits the system.

The Morley CR-6EA is a six-way changeover relay output module with built-in loop isolation for addressable fire systems. It ships complete with a rotary address switch and plug-in terminal blocks for straightforward installation and servicing. The module requires the M200-SMB-MM for mounting.

Technical overview

CR-6EA is Morley Addressable Devices' six-way changeover relay output module for addressable fire detection loops running the System Sensor protocol. Six Form C relays occupy one interface, each presenting an isolated dry changeover contact that can be wired for normally open or normally closed duty, so a single loop position switches six independently controlled circuits.

Addressing across the six relays follows from one rotary-switch setting: the module takes consecutive addresses on the loop, and surplus positions — up to three — can be disabled where fewer circuits are needed. Loop isolation is built in, individual LED indicators show status at the unit, and supervision does not extend to the switched circuit.

Removable plug-in terminal blocks keep the field wiring serviceable, and mounting requires the M200-SMB-MM. Terminal connection detail for each circuit is set out in the installation manual.

Specifications

Full technical data for this part.

relay_typeThe CR-6EA consists of six Form C relays
relay_contactsA single isolated set of dry relay contacts, which can be wired as normally open or normally closed, is provided for each address
relay_contact_ratings3A at 30VDC Resisitive Load
relay_current30mA/relay pulse 15.6ms duration, pulse under panel control
maximum_current1.49mA (Blinking LED once every 5 seconds) 36mA at 32V assuming all six relays have switched once and all six LEDs solid on
AddressingThe first address is set from 01 to 94; the other modules are automatically assigned the next five addresses; up to three unused addresses can be disabled
supervisionThe controlled circuit is not supervised
integral_isolatorbuilt-in loop isolation
address_switchRotary address switches
terminal_blocksRemovable plug–in terminal blocks
IndicatorsIndividual LED indicators
protocolSystem Sensor Protocol Output Modules

Specifications sourced from manufacturer documentation.