Addressable Audio Visual Devices
Morley BSO-PP-I00 EN54-23 Detector Base Strobe (VAD)
- integral_isolator
- with isolator
- Dimensions
- Height: 64mm Diameter:121mm
- Weight
- 202g
- max_current_consumption
- < 10.5mA (High Volume Tone 21 @24V)
- Operating Temperature
- -25°C to +70°C
- Relative Humidity
- Max. 95% relative humidity (non-condensing)
- IP Rating
- Optional IP65 rating
Overview
What it is and how it fits the system.
The Gent BSO-PP-I00 is a modular, high-output loop-powered intelligent detector base strobe, classified EN54-23 Category C, intended to alert all building occupants of a potential fire. Integrating the strobe into the detector base, it draws power and signalling from the addressable loop.
Technical overview
BSO-PP-I00 is an addressable loop-powered base sounder, featuring an integral isolator and designed for fire alarm applications. It is a Pure White Body c/w Isolator unit, approved to EN54-3 standards, and operates on the System Sensor Protocol.
The device has a height of 64mm and a diameter of 121mm, weighing 202g. It draws less than 10.5mA at high volume Tone 21 when powered at 24V and offers 32 built-in tones; rotary decade switches set the device address. An anti-tamper feature is incorporated for security.
Operating temperature ranges from -25°C to +70°C with a maximum relative humidity of 95% non-condensing. Low power requirements are supported, and an optional IP65 rating is available for enhanced environmental protection. It is compatible with white and ivory cover plates for base sounders.
Specifications
Full technical data for this part.
| integral_isolator | with isolator |
|---|---|
| Dimensions | Height: 64mm Diameter:121mm |
| Weight | 202g |
| max_current_consumption | < 10.5mA (High Volume Tone 21 @24V) |
| Operating Temperature | -25°C to +70°C |
| Relative Humidity | Max. 95% relative humidity (non-condensing) |
| built_in_tones | 32 built-in tones |
| address_switches | Rotary decade address switches |
| anti_tamper | Anti-Tamper feature |
| IP Rating | Optional IP65 rating |
| low_power | Low power requirements |
| protocol | System Sensor Protocol |
Specifications sourced from manufacturer documentation.