VESDA Heater kit for reflective beam detector. Requires 24V supply
| Part no. | BEAMHK |
|---|---|
| Brand | VESDA |
| Range | Beam Detection OSID Range |
| Sub-range | Beam Detection |

Image for illustration; item supplied may differ
Description
The System Sensor BEAMHK is a Heating Kit for use with the Transmitter/ Receiver Unit of Reflected Beam Smoke Detectors, for environments prone to the formation of condensation. Voltage: 15 to 32 V, Nominal: 1.6 W at 24 V.
The BEAMHK is a System Sensor Heating Kit for use with the Transmitter/ Receiver Unit of Reflected Beam Smoke Detectors.
Read the full technical description
The BEAMHK is a System Sensor Heating Kit for use with the Transmitter/ Receiver Unit of Reflected Beam Smoke Detectors.
The BEAMHK allows the transmitter/receiver of the reflected beam smoke detectors to operate in environments prone to the formation of condensation. The kit includes the following parts: 1 Transmitter/Receiver Heater Assembly.
Electrical specifications are Voltage: 15 to 32 V, Current: 92mA max at 32 V, Power Consumption Nominal: 1.6 W at 24 V and Maximum: 3 W at 32 V. The power supply must be capable of powering the heater, and other devices that may be supplied through the same terminals.
The heater is intended for the prevention of condensation only. It is not intended to increase or reduce the specified operating temperature range of the beam smoke detector. Align/realign beam smoke detector.
Specifications
| Voltage | 15 to 32 V |
|---|---|
| Current | 92mA max at 32 V |
| Power consumption nominal | Nominal: 1.6 W at 24 V |
| Power consumption maximum | Maximum: 3 W at 32 V |
| Package contents | 1 Transmitter/Receiver Heater Assembly |
| Document number | I56-2556-002 |
| Warranty | Three-year limited warranty; free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture |
| Heater function note | The heater is intended for the prevention of condensation only. It is not intended to increase or reduce the specified operating temperature range of the beam smoke detector. |
| Current requirement note | The electrical current specified is the requirement for the heater only. The power supply must be capable of powering the heater, and other devices that may be supplied through the same terminals. |
Specifications per manufacturer documentation, subject to change. E&OE.