ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Morley ZXSe Panels

Morley ZX5Se Addressable Fire Panel 797-064 (5-Loop)

Loop capacity
ZX5Se Loop Capacity: 1 to 5 loops 460mA per loop maximum
Zones
200 (max)
Zonal indicators
LED TYPE ZONAL INDICATORS FIRE/FAULT/TEXT/DISABLED: 20 (Up to 200 available on special request)
Internal sounder
Yes
Serial interface
3 serial ports with connections for optional RS485 or RS232 plug-in communication cards
Auxiliary relays
EN54 format at 1 fault relay and 1 programmable relay voltage free, changeover outputs contacts rated at 24V AC/DC, 1A, 0.6 pF maximum
Sounder outputs
4 Programmable outputs. Open and short circuit monitoring. 1A maximum per output (Maximum total load 1.3A)

Overview

What it is and how it fits the system.

The Morley 797-064 is a ZX5Se intelligent fire alarm control panel within the Morley-IAS ZXSe range, configurable from one to five loops at 460mA per loop across up to 200 zones. It provides 20 LED zonal indicators (up to 200 on special request), an internal sounder and four programmable, fully monitored sounder outputs. EN54-format relays and three serial ports support integration into larger fire systems.

Technical overview

797-064 refers to a Morley-IAS ZX5Se Fire Alarm Control Panel in the ZXSE range and anchors a broad set of ZX5Se fitting options, being listed alongside a glass door kit, a bezel kit and the ZX5SE battery box. One to five loops can be driven, each held within a 460 mA ceiling, across a maximum of 200 zones.

LED type zonal indication covers fire, fault, text and disabled states — twenty positions in the base configuration, rising to 200 on special request — and the panel carries its own internal sounder. User control runs from Sound Alarms through to System Reset, with programming handled on an alphanumeric multi-level keypad; output duty rests on four supervised programmable sounder circuits and EN54-format relay provision.

Communication expands through three serial ports for the optional RS485 or RS232 plug-in cards, and the 795-057 MODBUS interface unit requires the RS485 card to be in place. The wider hardware list spans PCB-only modules — 4-way relay, 8-way input, 4-way sounder, a 40-way programmable mimic interface and the Hi-485 communication module — plus 20-zone and 60-zone LED display indicator cards, internal and external remote printer options, a Morley-IAS 460 mA loop driver card and a USB isolated upload/download lead. Remote indication falls to the ZXr-P passive repeater, the ZXr-A active repeater adds key-switch-activated silence, reset, mute and evacuate-all controls, and terminal connections and physical wiring belong to the installation manual.

Specifications

Full technical data for this part.

Loop capacityZX5Se Loop Capacity: 1 to 5 loops 460mA per loop maximum
Zones200 (max)
Zonal indicatorsLED TYPE ZONAL INDICATORS FIRE/FAULT/TEXT/DISABLED: 20 (Up to 200 available on special request)
Internal sounderYes
Serial interface3 serial ports with connections for optional RS485 or RS232 plug-in communication cards
Auxiliary relaysEN54 format at 1 fault relay and 1 programmable relay voltage free, changeover outputs contacts rated at 24V AC/DC, 1A, 0.6 pF maximum
Sounder outputs4 Programmable outputs. Open and short circuit monitoring. 1A maximum per output (Maximum total load 1.3A)

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Optional accessories

Optional additions — this product works without them.