Morley DXc4 Four Loop Fire Alarm Control Panel
- Operating voltage
- 110 / 230V AC +/-15% (DXc4)
- Psu rating
- 24V DC 4A (DXc4)
- Auxiliary output
- +24V DC 250mA fused (DXc4)
- Loop capacity
- 500mA per loop
- Loop driver
- 500mA multi-protocol loop driver
- Sounder circuits
- 2 output circuits, 1A per circuit
- Operating temperature
- 0°C to +40°C
Overview
What it is and how it fits the system.
The Morley-IAS DXc4 is a 1, 2 and 4 loop, networkable, multi-protocol analogue addressable fire alarm control panel from the DX Connexion range. It operates from 230 V AC (±15 %) with a 24 V DC 4 A PSU, 500 mA multi-protocol loop drivers and a +24 V DC 250 mA fused auxiliary output. Two monitored 1 A sounder circuits, single-pole-changeover fire and fault relays and two onboard monitored inputs provide scalable control for larger sites.
Technical overview
714-001-241 designates the Morley DXc4, the four-loop analogue addressable fire alarm control panel in the networkable, multi-protocol DX Connexion family. Set-up follows a five-key-press routine, configurations move over USB upload and download, and there is the option to upload a company logo; seven-day timers, event logging, onboard diagnostics and a class change function round out the software set alongside PC configuration software.
False alarm management works through coincidence and verification detection, with sensitivity adjustment — between day and night, for example. Loop devices follow one protocol per panel, chosen from Apollo (Xplorer, XP95 and Discovery), Hochiki (ESP) and System Sensor, and each of the four loops is driven at up to 500 mA by its multi-protocol loop driver.
On larger sites, four DXc4 panels can be joined to reach the 16-loop network maximum, with mixed loop sizes equally permitted; the network is true peer-to-peer, fault tolerant and BS5839 part 1 compliant. Field terminations use plug-in connectors, while physical connection and field-wiring detail is left to the installation manual.
Among the recommended accessories are the 795-097 software programming kit, which spans the same System Sensor, Apollo and Hochiki protocols, and the 795-115 flush bezel kit for panels fitted with the extension backbox.
Specifications
Full technical data for this part.
| Order code | 714-001-241 DXc4 Four loop Fire Alarm Control Panel |
|---|---|
| Operating voltage | 110 / 230V AC +/-15% (DXc4) |
| Psu rating | 24V DC 4A (DXc4) |
| Auxiliary output | +24V DC 250mA fused (DXc4) |
| Loop capacity | 500mA per loop |
| Loop driver | 500mA multi-protocol loop driver |
| Sounder circuits | 2 output circuits, 1A per circuit |
| Output relays | Fire relay: Single pole changeover 24V DC 1A; Fault relay: Single pole changeover 24V DC 1A; Aux relay: Programmable single pole changeover 24V DC 1A |
| Onboard monitored inputs | 2 x onboard monitored inputs |
| Onboard data ports | 1 x RS485 (Repeater connection), 1 x PC Programming Port |
| Optional ports | RS232 third party protocol interface |
| Weight | 4.5kg (Excluding Batteries) (DXc4) |
| Operating temperature | 0°C to +40°C |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
DXc Software programming kit (SPK) supports System Sensor, Apollo and Hochiki protocols
compatible / works with: DXc Software programming kit (SPK) supports System Sensor, A
Flush bezel kit for DXc 2/4 (medium enclosure)
Bezel kit listed for the DXc2/4 panels.
Flush bezel kit for DXc 2/4 with the extension backbox fitted (medium enclosure)
Bezel kit plus extension box listed for the DXc2/4 panels.
Rack Mount Bracket for DXc2/4
Rack mounting kit listed for the DXc2/4 panels.
Hand Held Printer - Thermal Type 58mm
Panel supports connection of the PRINTER-HAND external handheld printer (available separately).