- Operating voltage
- 230V AC (+15%,-15%) 50-60 Hz
- Operating voltage (alt datasheet)
- 110 / 230V AC +/-15%
- Psu rating
- 24V DC 4A
- Auxiliary output
- +24V DC 250mA fused
- Stand-by batteries
- 2 x 17Ah (Not included)
- Loop capacity
- 500mA per loop
- Operating temperature
- 0°C to +40°C
Overview
What it is and how it fits the system.
The Morley-IAS DXc2 is a two-loop, networkable, multi-protocol analogue addressable fire alarm control panel from the DX Connexion range. It runs from 230 V AC (±15 %) with a 24 V DC 4 A PSU, a 500 mA multi-protocol loop driver and a +24 V DC 250 mA fused auxiliary output. Two monitored sounder circuits at 1 A each, plus single-pole-changeover fire and fault relays, support flexible system integration with provision for 2 x 17 Ah standby batteries.
Technical overview
714-001-221 is the two-loop DXc2 fire alarm control panel from Morley's DX Connexion range of networkable analogue addressable panels. Each of the two loops draws on a 500 mA multi-protocol loop driver, and the panel takes Apollo Xplorer, XP95 and Discovery devices, Hochiki ESP devices or System Sensor protocol devices, with a single protocol selected within the control panel.
Day-to-day control runs through a six-line, 40-character backlit blue liquid crystal display and a twelve-button alphanumeric keypad, with dedicated control keys running from evacuate through to system reset and show alarm zones. Two independent programmable function keys carry their own LED indicators, up to 80 fire zones can be used with or without zone LEDs, and a battery-backed real-time clock is fitted.
Where a single panel cannot cover the site, DXc panels network peer-to-peer with fault tolerance up to a 16-loop maximum — eight two-loop panels, or any mix of loop sizes — on a BS5839 part 1 compliant network, and an onboard RS485 port handles the repeater connection. Standby provision is based on 2 x 17Ah batteries.
Recommended accessories from the same range span the 795-113 flush bezel kit for the medium enclosure, the 795-120 rack mounting bracket for DXc2/4, and the PRINTER-HAND 58 mm thermal handheld printer, whose connection the panel supports.
Specifications
Full technical data for this part.
| Order code | 714-001-221 DXc2 Two loop Fire Alarm Control Panel |
|---|---|
| Operating voltage | 230V AC (+15%,-15%) 50-60 Hz |
| Operating voltage (alt datasheet) | 110 / 230V AC +/-15% |
| Psu rating | 24V DC 4A |
| Auxiliary output | +24V DC 250mA fused |
| Stand-by batteries | 2 x 17Ah (Not included) |
| Loop capacity | 500mA per loop |
| Loop driver | 500mA multi-protocol loop driver |
| Sounder circuits | 2 output circuits, 1A per circuit |
| Output relays | Fire relay: Single pole changeover 24V DC 1A; Fault relay: Single pole changeover 24V DC 1A; Aux relay: Programmable single pole changeover 24V DC 1A |
| Onboard monitored inputs | 2 x onboard monitored inputs |
| Weight (excluding batteries) | 4.5kg |
| Operating temperature | 0°C to +40°C |
| Relative humidity | 5% - 95% non-condensing |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
DXc Software programming kit (SPK) supports System Sensor, Apollo and Hochiki protocols
compatible / works with: DXc Software programming kit (SPK) supports System Sensor, A
Flush bezel kit for DXc 2/4 (medium enclosure)
Bezel kit listed for the DXc2/4 panels.
Flush bezel kit for DXc 2/4 with the extension backbox fitted (medium enclosure)
Bezel kit plus extension box listed for the DXc2/4 panels.
Rack Mount Bracket for DXc2/4
Rack mounting kit listed for the DXc2/4 panels.
Hand Held Printer - Thermal Type 58mm
Panel supports connection of the PRINTER-HAND external handheld printer (available separately).
Datasheets & documents
Reference downloads.
- 1664 KB
- 1394 KB