Morley DXc1 1-Loop Addressable Fire Alarm Panel, IP30

Operating voltage
230V AC (+15%,-15%) 50-60 Hz
Operating temperature
0°C to +40°C
Relative humidity
5% - 95% non-condensing
Material
Mild steel sheet rear enclosure. ABS plastic front cover to BS EN60950. All displays and controls are carried on the enclosure door.
Dimensions [mm] (h x w x d)
260 x 390 x 147
Weight (excluding batteries)
4kg
Ip rating
IP30 (EN6059)

Overview

What it is and how it fits the system.

The Morley DXc1 is a one-loop fire alarm control panel running from 230 V AC (±15 %, 50–60 Hz) with a 24 V DC 2 A power supply. Its mild steel rear enclosure and ABS front cover are rated IP30 and finished in RAL 9002 grey white, measuring 260 x 390 x 147 mm and weighing 4 kg excluding batteries. Twenty-five top and two bottom 20 mm knockouts ease cable entry on compact installations.

Technical overview

714-001-111 is the order code for the Morley DXc1, the one-loop fire alarm control panel in the Morley DXc range. Multi-protocol working defines the DXc platform: the panel accepts Apollo devices from the Xplorer, XP95 and Discovery families, Hochiki ESP devices and System Sensor protocol devices.

Every display and control sits on the enclosure door, and the electronics run from a 230 V AC mains connection through an internal power supply delivering 24 V DC at up to 2 A, with a fused auxiliary output for ancillary equipment. Two sounder circuits are provided at 1 A per circuit. On the data side, an onboard RS485 port is dedicated to repeater connection, a PC programming port handles configuration, and an optional RS232 port opens a third-party protocol interface.

Programming support comes from the 795-097 DXc software programming kit, which spans the same System Sensor, Apollo and Hochiki protocols. For recessed installation the 795-112 flush bezel kit suits the DXc1 small enclosure, with the 795-114 kit covering panels fitted with the extension backbox, and the PRINTER-HAND 58 mm thermal handheld printer can be connected to the panel.

Specifications

Full technical data for this part.

Operating voltage230V AC (+15%,-15%) 50-60 Hz
Operating temperature0°C to +40°C
Relative humidity5% - 95% non-condensing
MaterialMild steel sheet rear enclosure. ABS plastic front cover to BS EN60950. All displays and controls are carried on the enclosure door.
Dimensions [mm] (h x w x d)260 x 390 x 147
Weight (excluding batteries)4kg
ColourRAL 9002 - Grey white
Ip ratingIP30 (EN6059)
Knockouts (20mm)Top: 25x Bottom: 2x
Psu rating24V DC 2A
Auxilliary output 1+24V DC 250mA fused
Stand-by batteries2 x 7Ah
Stand-by battery durationStand alone: 24 hours back-up with either network card or repeater connected: 48 hours
Sounder circuits2 output circuits, 1A per circuit.

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Optional accessories

Optional additions — this product works without them.

795-097

DXc Software programming kit (SPK) supports System Sensor, Apollo and Hochiki protocols

compatible / works with: DXc Software programming kit (SPK) supports System Sensor, A

£231.15
ex VAT
£277.38 inc VAT
Sold separately
795-112

Flush bezel kit for DXc1 (small enclosure)

Bezel kit listed for the DXc1 panel.

£138.14
ex VAT
£165.77 inc VAT
Sold separately
795-114

Flush bezel kit for DXc 1 with the extension backbox fitted (small enclosure)

Bezel kit plus extension box listed for the DXc1 panel.

£157.87
ex VAT
£189.44 inc VAT
Sold separately
PRINTER-HAND

Hand Held Printer - Thermal Type 58mm

Panel supports connection of the PRINTER-HAND external handheld printer (available separately).

£1,131.03
ex VAT
£1,357.24 inc VAT
Sold separately

Datasheets & documents

Reference downloads.