Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Gent, Morley-IAS and Xtralis stock added weekly. Open to the trade.

Morley-IAS DXc1 Single loop panel (no zone LEDs) 230Vac, 2 sounder circuits. Supports Apollo, System Sensor and Hochiki protocols. 260 x 390 x 147mm (H x W x D).

Part no.714-001-111
BrandMorley-IAS
RangeMorley DXc Panels
Sub-rangeFire Panel
Morley 714-001-111 DXc1 Single loop panel — blue screen, keypad, and control buttons

Image for illustration; item supplied may differ

At a glance

  • Single Loop Addressable Panel714-001-111 is the DXc1 SINGLE LOOP CONTROL PANEL from the DXc Intelligent Multi-Protocol Fire Alarm Control Panel range.
  • Multi Protocol LoopThe panel works with Apollo, System Sensor and Hochiki protocols.
  • Mains Supply And PSUOperating voltage is 230 V, 50-60 Hz AC (+15%,-15% tolerance) with a maximum PSU rating of 2 A / 24 V DC.
  • Monitored Sounder CircuitsTwo programmable output sounder circuits are monitored and rated at 1 A.
  • Graphic LCD DisplayA 240x64 pixels LCD graphic display shows 6x40 characters in blue liquid crystal with backlight illumination.
  • Networking To 16 LoopsThe panel can operate as a stand-alone or networked system with other DXc series panels up to 16 loops.
  • Steel And ABS EnclosureA Mild Steel rear enclosure with an ABS plastic front cover complying BS EN60950 is gray white, similar to RAL 9002, and rated IP30.
  • EN54 SpecificationThe panel is specified to EN54-2 and EN54- 4.

Description

714-001-111 is the single loop member of the DXc Intelligent Multi-Protocol Fire Alarm Control Panel range, an addressable panel that drives Apollo, System Sensor or Hochiki devices on one loop of up to 500 mA across 160 Fire Zones.

Supply is 230 V, 50-60 Hz AC (+15%,-15% tolerance) with a maximum PSU rating of 2 A / 24 V DC and a battery capacity of 2 x 12 V / 7 Ah. Outputs run to two monitored sounder circuits at 1 A, an auxiliary 24 V DC / 250 mA feed, Fire, Fault and Auxiliary relays, and a 7 day timer with onboard diagnostic. Configuration is by Keypad and PC, and a company logo can be uploaded to the display.

714-001-111 is the DXc1 single loop control panel, an addressable multi protocol fire detection system within the DXc Intelligent Multi-Protocol Fire Alarm Control Panel range. It works with Apollo, System Sensor and Hochiki protocols, offers 160 Fire Zones and can run stand-alone or networked with other DXc series panels up to 16 loops.

Mains input is 230 V, 50-60 Hz AC (+15%,-15% tolerance) feeding a 2A power source whose maximum rating is 2 A / 24 V DC. Loop load reaches 500 mA, the two monitored programmable output sounder circuits are rated 1 A, and a fixed auxiliary output is joined by a resettable 24 V DC / 250 mA output. A general relay for alarm and fault sits beside one programmable relay.

The fascia carries a 240x64 pixels LCD graphic display of 6x40 characters in blue liquid crystal with backlight illumination, plus optional 40, 80 or 160 zone alarm LEDs. Two keys and two inputs handle programmable functions, an integrated USB port takes PC programming and an RS-485 port links peripherals such as repeaters.

Read the full technical description

Cable entry is by 25 x 20 mm knock-outs at the top and 2 x 20 mm knock-outs at the bottom of the IP30 enclosure, and the panel is specified to EN54-2 and EN54- 4. A rack mount kit, part No. 795-119, and a flush bezel, part No. 795-112, fit this panel, and spares extend to a 795-106 DXc1 Spare PSU.

714-001-111 is the DXc1 single loop control panel, an addressable multi protocol fire detection system within the DXc Intelligent Multi-Protocol Fire Alarm Control Panel range. It works with Apollo, System Sensor and Hochiki protocols, offers 160 Fire Zones and can run stand-alone or networked with other DXc series panels up to 16 loops.

Mains input is 230 V, 50-60 Hz AC (+15%,-15% tolerance) feeding a 2A power source whose maximum rating is 2 A / 24 V DC. Loop load reaches 500 mA, the two monitored programmable output sounder circuits are rated 1 A, and a fixed auxiliary output is joined by a resettable 24 V DC / 250 mA output. A general relay for alarm and fault sits beside one programmable relay.

The fascia carries a 240x64 pixels LCD graphic display of 6x40 characters in blue liquid crystal with backlight illumination, plus optional 40, 80 or 160 zone alarm LEDs. Two keys and two inputs handle programmable functions, an integrated USB port takes PC programming and an RS-485 port links peripherals such as repeaters.

A mild steel rear enclosure and ABS plastic front cover complying BS EN60950 are finished gray white, similar to RAL 9002, and rated IP30. The panel measures H: 260 mm W: 390 mm D: 147 mm, weighs 4 kg and works from 0°C to 40°C at 5% to 95% non-condensing.

Specifications

Operating voltage230V AC (+15%,-15%) 50-60 Hz
Operating temperature0°C to +40°C
Relative humidity5% - 95% non-condensing
MaterialMild steel sheet rear enclosure. ABS plastic front cover to BS EN60950. All displays and controls are carried on the enclosure door.
Dimensions [mm] (h x w x d)260 x 390 x 147
Weight (excluding batteries)4kg
ColourRAL 9002 - Grey white
Ip ratingIP30 (EN6059)
Knockouts (20mm)Top: 25x Bottom: 2x
Psu rating24V DC 2A
Auxilliary output 1+24V DC 250mA fused
Stand-by batteries2 x 7Ah
Stand-by battery durationStand alone: 24 hours back-up with either network card or repeater connected: 48 hours
Sounder circuits2 output circuits, 1A per circuit.

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Datasheet (714-001-111, 714-001-221, 714-001-241)Datasheet1.6 MBDownload PDF
Datasheet (714-001-111, 714-001-221, 714-001-241)Datasheet1.4 MBDownload PDF

Optional accessories