Part Number or the Week S3EP-V-VAD-HPR-R

Honeywell 4 Ch 250W Class D Amp w/ Inbuilt Batt Ch

Part no.585031
BrandHoneywell
RangeV1 Voice Rack
Sub-rangeRack Components
Honeywell 585031 4 x 250 W Voice Alarm Amplifier — front view with grille, status LEDs and green ring button

Image for illustration; item supplied may differ

At a glance

  • Four Channel Class D AmplifierThe 4XD250B delivers 4 x 250 W from four channels built in Class D technology.
  • 2 HU Rack FormatThe unit is 2U 19inch rack mountable at W: 483 mm H: 90 mm D: 402 mm (2 HU) and weighs approx. 11,5 kg.
  • Inbuilt Battery ChargerThe unit has an integral battery charger for charging 24V lead acid batteries of up to 105Ah used to provide standby supply in the event of mains failure.
  • Mains and Emergency SupplyRated voltage is 230 V AC, +10 %/-5 %, with an emergency power supply range of 21,5 V DC … 28,5 V DC.
  • Programmable Backup ChannelOne channel may be programmed as a backup channel for the other 3 channels or for amplifier channels of other amplifiers with the same or lower output power.
  • Power Save ModeAn inbuilt Power Save mode is part of the amplifier.
  • EN 54 ApprovalsThe amplifier holds EN 54-4 and EN 54-16 approvals.
  • Direct Controller IntegrationDirect integration with the GNP Controller, VARIODYN®Dl DOM module is supported.

Description

This amplifier is intended for VARIODYN ONE and integrates directly with GNP Controller, VARIODYN®Dl DOM, which also handles system control and monitoring. Four 100V outputs are brought out at the rear of the unit for that module, and the control inputs use a connector marked CONTROL I/F.

Because all amplifier channels are completely independent from each other, one of them can be programmed as a backup channel, either for the other 3 channels or for amplifier channels of other amplifiers with the same or lower output power. An inbuilt Power Save mode and an intuitive display interface for device status round out the operating arrangements.

The 4XD250B, part number 585031, is a 2U 19inch rack mountable direct drive voice alarm amplifier holding four independent Class D channels rated 4 x 250 W, and it takes up 2 HU of rack height. Every channel carries its own independent 100V audio output, rated into a load of 40 Ω.

Rated voltage is 230 V AC, +10 %/-5 %, drawing 2.2 A at 230 V AC and 18.6 A at 24 V DC, rising to 53.5 A for a 1 kHz sinus burst of 1 min. An F10AH250V fuse protects the mains inlet, emergency power supply runs 21,5 V DC … 28,5 V DC, and the inbuilt charger serves a valve regulated lead-acid battery of 65AH min-105AH max at up to 6.5A. Where the standby supply is external, the temperature sensor must not be connected at the connector marked BATT TEMP, and the internal charger must be configured as disabled.

Read the full technical description

Measured performance includes a signal to noise ratio of ≥ 90 dB (A), channel separation of ≥ 75 dB, a distortion factor at 1 kHz of ≤ 0,3 %, an input level of 0 dBu and a system input impedance of 20 kOhm. The external batteries take their charge from the integral temperature compensated charger. Should the standby supply be external, the temperature sensor must not be connected at the connector marked BATT TEMP, and the internal charger must be configured as disabled.

The 4XD250B, part number 585031, is a 2U 19inch rack mountable direct drive voice alarm amplifier holding four independent Class D channels rated 4 x 250 W, and it takes up 2 HU of rack height. Every channel carries its own independent 100V audio output, rated into a load of 40 Ω.

Rated voltage is 230 V AC, +10 %/-5 %, drawing 2.2 A at 230 V AC and 18.6 A at 24 V DC, rising to 53.5 A for a 1 kHz sinus burst of 1 min. An F10AH250V fuse protects the mains inlet, emergency power supply runs 21,5 V DC … 28,5 V DC, and the inbuilt charger serves a valve regulated lead-acid battery of 65AH min-105AH max at up to 6.5A. Where the standby supply is external, the temperature sensor must not be connected at the connector marked BATT TEMP, and the internal charger must be configured as disabled.

Weight is approx. 11,5 kg in a RAL 810-M enclosure of W: 483 mm H: 90 mm D: 402 mm (2 HU). Ambient temperature is -5 °C ... 55 °C with air humidity < 93 % (non-condensing). Idle heat dissipation on mains comes to 60Wmax., rising to 33Wmax. on battery when the channels are enabled. The approvals held are EN 54-4 and EN 54-16.

Specifications

ModelAMP 4XD250B
Output power4 x 250 W
TechnologyClass D
ApprovalEN 54-4 and EN 54-16
Rated voltage230 V AC, +10 %/-5 %
Emergency power supply21,5 V DC … 28,5 V DC
Rated current 230v ac2.2 A
Rated current 24v dc18.6 A
Current 1khz sinus 1min 24v dc53.5 A
Efficiency< 80 %
Transmission range50 Hz ... 60 Hz
System input impedance20 kOhm
Input level0 dBu
Distortion factor 1khz≤ 0,3 %