Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Morley-IAS HRZ-8e, 8 Zone Non-Addressable Fire Alarm Control Panel. 8 detection zones, 2 sounder outputs, surface mounting, fire and fault relays. 318 x 356 x 92mm (H x W x D)

Part no.002-492-282
BrandMorley-IAS
RangeConventional Horizon Panels
Sub-rangeFire Panel
Morley-IAS 002-492-282 Horizon HRZ8E 8-Zone Fire Panel — white case, blue faceplate, horizon logo, label strips, key lock.

Image for illustration; item supplied may differ

Description

The Morley-IAS Horizon HRZ8E is an 8-zone conventional fire alarm control panel from the Horizon HRZ Series, supplied complete with the 020-713 fire & fault relay. It accepts 2, 4 or 8 detection circuits at 2mA per circuit (typically more than 20 detectors each) and provides two monitored sounder outputs rated 0.5A per circuit plus a 0.5A auxiliary output. Fed from a 230Vac supply with an 18.5 to 28.5Vdc internal source rated 1.8A, it covers larger eight-zone conventional schemes within a single panel.

002-492-282 is an 8 zone Non-Addressable fire alarm control panel from the Conventional Horizon Panels range. It provides 8 detection circuits, two monitored sounder outputs rated at 0.5 Amps each, and fire and fault relays. The panel operates from a 230 Vac 50/60 Hz supply with a ±15% tolerance and delivers an internal DC output between +18.5 and +28.5 Vdc, capable of supplying up to 1.8 Amps maximum while limiting alarm load to 1 Amp.

Read the full technical description

002-492-282 is an 8 zone Non-Addressable fire alarm control panel from the Conventional Horizon Panels range. It provides 8 detection circuits, two monitored sounder outputs rated at 0.5 Amps each, and fire and fault relays. The panel operates from a 230 Vac 50/60 Hz supply with a ±15% tolerance and delivers an internal DC output between +18.5 and +28.5 Vdc, capable of supplying up to 1.8 Amps maximum while limiting alarm load to 1 Amp.

Standby power is supported by sealed lead-acid batteries, with minimum capacity of 2 x 12 V 2.8Ah and maximum of 2 x 12 V 7Ah. An auxiliary output provides the same DC voltage range at up to 0.5 Amp, and 22 configurable digital inputs are available for functions such as Class Change, Alert, Evacuate and Reset, triggered by extended closing contacts. The unit is housed in a fire retardant ABS plastic enclosure with IP30 rating, measuring 318 x 356 x 96 mm and weighing approximately 2 Kg without batteries.

Optional enhancements include a relay card providing one fire relay with changeover contacts rated at 30Vdc and 1 Amp. Compatibility extends to Apollo Series 60, Series 65 and Orbis detectors, as well as System Sensor ECO1000 and Series 300 devices. Additional accessories such as the Horizon Relay Kit (order code 020-713), Active End Of Line Kit (020-417), and various input/output cards are available for expanded functionality.

Specifications

Panel type2, 4 & 8 Zone Conventional Fire Alarm Control Panels
Zones8 Zone (HRZ8E)
Detection circuits2, 4 or 8 detection circuits
Detection circuit current2 mA per circuit (typically >20 detectors)
Operating voltage230 Vac 50/60 Hz (±15%)
Internal power supply output voltage+18.5 to +28.5 Vdc
Output current1.8 Amps maximum
Maximum alarm load1 Amp
Sounder outputs2 monitored outputs, 0.5 Amps per circuit
Auxiliary output+18.5 to +28.5 Vdc, 0.5 Amp. (max)
Optional relay card1 x Fire relay (changeover contacts rating 30Vdc, 1 Amp)
Digital inputs22 configurable inputs (Class Change, Alert, Evacuate, Reset)
Digital input triggerExtended closing contact
Standby battery typeSealed lead acid

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Datasheet (002-492-222, 002-492-242, 002-492-282)Datasheet174 KBDownload PDF
Datasheet (002-492-222, 002-492-242, 002-492-282, 020-417, 020-713 +4 more)Datasheet2.1 MBDownload PDF

Optional accessories