Morley-IAS HRZ-8e, 8 Zone Non-Addressable Fire Alarm Control Panel. 8 detection zones, 2 sounder outputs, surface mounting, fire and fault relays. 318 x 356 x 92mm (H x W x D)
| Part no. | 002-492-282 |
|---|---|
| Brand | Morley-IAS |
| Range | Conventional Horizon Panels |
| Sub-range | Fire Panel |

Image for illustration; item supplied may differ
Description
The Morley-IAS Horizon HRZ8E is an 8-zone conventional fire alarm control panel from the Horizon HRZ Series, supplied complete with the 020-713 fire & fault relay. It accepts 2, 4 or 8 detection circuits at 2mA per circuit (typically more than 20 detectors each) and provides two monitored sounder outputs rated 0.5A per circuit plus a 0.5A auxiliary output. Fed from a 230Vac supply with an 18.5 to 28.5Vdc internal source rated 1.8A, it covers larger eight-zone conventional schemes within a single panel.
002-492-282 is an 8 zone Non-Addressable fire alarm control panel from the Conventional Horizon Panels range. It provides 8 detection circuits, two monitored sounder outputs rated at 0.5 Amps each, and fire and fault relays. The panel operates from a 230 Vac 50/60 Hz supply with a ±15% tolerance and delivers an internal DC output between +18.5 and +28.5 Vdc, capable of supplying up to 1.8 Amps maximum while limiting alarm load to 1 Amp.
Read the full technical description
002-492-282 is an 8 zone Non-Addressable fire alarm control panel from the Conventional Horizon Panels range. It provides 8 detection circuits, two monitored sounder outputs rated at 0.5 Amps each, and fire and fault relays. The panel operates from a 230 Vac 50/60 Hz supply with a ±15% tolerance and delivers an internal DC output between +18.5 and +28.5 Vdc, capable of supplying up to 1.8 Amps maximum while limiting alarm load to 1 Amp.
Standby power is supported by sealed lead-acid batteries, with minimum capacity of 2 x 12 V 2.8Ah and maximum of 2 x 12 V 7Ah. An auxiliary output provides the same DC voltage range at up to 0.5 Amp, and 22 configurable digital inputs are available for functions such as Class Change, Alert, Evacuate and Reset, triggered by extended closing contacts. The unit is housed in a fire retardant ABS plastic enclosure with IP30 rating, measuring 318 x 356 x 96 mm and weighing approximately 2 Kg without batteries.
Optional enhancements include a relay card providing one fire relay with changeover contacts rated at 30Vdc and 1 Amp. Compatibility extends to Apollo Series 60, Series 65 and Orbis detectors, as well as System Sensor ECO1000 and Series 300 devices. Additional accessories such as the Horizon Relay Kit (order code 020-713), Active End Of Line Kit (020-417), and various input/output cards are available for expanded functionality.
Specifications
| Panel type | 2, 4 & 8 Zone Conventional Fire Alarm Control Panels |
|---|---|
| Zones | 8 Zone (HRZ8E) |
| Detection circuits | 2, 4 or 8 detection circuits |
| Detection circuit current | 2 mA per circuit (typically >20 detectors) |
| Operating voltage | 230 Vac 50/60 Hz (±15%) |
| Internal power supply output voltage | +18.5 to +28.5 Vdc |
| Output current | 1.8 Amps maximum |
| Maximum alarm load | 1 Amp |
|---|---|
| Sounder outputs | 2 monitored outputs, 0.5 Amps per circuit |
| Auxiliary output | +18.5 to +28.5 Vdc, 0.5 Amp. (max) |
| Optional relay card | 1 x Fire relay (changeover contacts rating 30Vdc, 1 Amp) |
| Digital inputs | 22 configurable inputs (Class Change, Alert, Evacuate, Reset) |
| Digital input trigger | Extended closing contact |
| Standby battery type | Sealed lead acid |
Specifications per manufacturer documentation, subject to change. E&OE.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Datasheet (002-492-222, 002-492-242, 002-492-282) | Datasheet | 174 KB | Download PDF |
| Datasheet (002-492-222, 002-492-242, 002-492-282, 020-417, 020-713 +4 more) | Datasheet | 2.1 MB | Download PDF |
Optional accessories
- 020-417Active End of Line Monitor Modulecompatible / works with: Active end of line monitor module£39.47ex VAT£47.36 inc VATIn stock
- 020-743Capacitor Kit for Detectors Not Compatible with Capacitive EOL Monitoring. Includes 8 x 10µƒ capacitors. Active EOL's required - See part number 020-417compatible / works with: Capacitor kit for detectors not compatible with capacitive E£31.63ex VAT£37.96 inc VATIn stock
- 020-7478-way Input / Output Card. Provides up to 8 configurable relay outputs or up to 4 command inputs and 4 outputscompatible / works with: 8-way input / output card. Provides up to 8 configurable rel£143.75ex VAT£172.50 inc VATIn stock
- 020-713Fire & Fault Relay Module for NFS2-8Optional fire & fault relay kit for the Horizon panel.£46.05ex VAT£55.26 inc VATIn stock